CERAMIC VACUUM INTERRUPTER FOR LOAD-BREAKING SWITCH
MAIN TECHNICAL DATA DB3.393.713WX
Data | Unit | Value |
Rated Voltage
| kV | 12 |
Lightning Impulse Withstand Voltage (Peak)
| kV | 75 |
Short-time (1min) Power-frequency Withstand Voltage | kV | 42/48 |
Rate Frequency | Hz | 50 |
Rated Current | A | 630 |
Rated Short-time Withstand Current | kA | 20 |
Rated Duration of Short-circuit | s | 4 |
Rated Peak Withstand Current | kA | 50 |
Rated Short-circuit Making Current | kA | 50 |
Rated Active Load Breaking Current | A | 630 |
Rated Closed-loop Breaking Current
| A | 630 |
Rated Single Capacitor Bank Breaking Current | A | 400 |
Rated Back-to-back Capacitor Bank Breaking Current | A | 400 |
Rated Breaking Current of Cable Charging | A | 10 |
Mechanical Endurance | Operations | 10000 |
Clearance Between Open Contacts | mm | 9±1 |
Contact Closed Force Due to Bellows and Atmosphere | N | 70±25 |
Counterforce of Contact at Full Stroke | N | 120±30 |
Circuit Resistance at Min. Rated Contact Force | μΩ | ≤30 |
Contact Limit Erosion | mm | 3 |
Mass of Moving Parts | kg | 0.4 |
Internal Gas Pressure | Pa | <1.33×10-3 |
Shelf Life | Year | 20 |
MECHANICAL DATA OF VACUUM SWITCH EQUIPPED WITH THE INTERRUPTERS
Data | Unit | Value |
Average Opening Speed | m/s | 1.0±0.2 |
Average Closing Speed | m/s | 0.6±0.2 |
Contact Bounce Duration at Closing Operation | ms | ≤2 |
Out of Simultaneity of Contact Closing and Opening | ms | ≤1 |
Rated Contact Pressure | N | 9001100 |
Max.rebound of contact at opening Operation | mm | 2 |
Overtravel during opening | mm | ≤2 |
Note 1: Within transformer oil or equivalent isolation medium.
Note 2: Rated characteristics to be given on request.
Note 3: Meets or exceeds the electrical endurance requirements of class E1 for autoreclosing duty per IEC60265-1 and GB/T3804-2004.