vacuum interrupter

vacuum interrupter
Product Detailed
Related Categories:Other Machinery
This vacuum interrupter is designed for 12KV, 400A vacuum contactors; for the outline drawing, please contact me NOW

CERAMIC VACUUM INTERRUPTER FOR CIRCUIT-BREAKER

MAIN TECHNICAL DATA        TYPE: TJC-12/400Y1(2314)

Data

Unit

Value

Rated Voltage

kV

12

Lightning Impulse Withstand Voltage (Peak)

kV

75

Short-time (1min) Power-frequency Withstand Voltage

kV

42

Rate Frequency

Hz

50

Rated Current

A

400

Rated Short-time Withstand Current

kA

4

Rated Duration of Short-circuit

s

4

Min.Rated Breaking Current

A

80

Max.Rated Breaking Current

kA

3.2

Limit Breaking Current

kA

4

Rated Making Current

kA

4

Rated Operating Frequency

Operations/h

120

Short-time Operating Frequency

Operations/h

1200

Electrical Endurance

AC-3

Operations

250000

AC-4

 

Operations

100000

Mechanical Endurance

Operations

300000

Clearance Between Open Contacts

mm

6±1

Contact Closed Force Due to Bellows and Atmosphere

N

70±20

Counterforce of Contact at Full Stroke

N

110±25

Circuit Resistance at Min. Rated Contact Force

μΩ

≤50

Contact Limit Erosion

mm

3

Mass of Moving Parts

kg

0.5

Internal Gas Pressure

Pa

<1.33×10-3

Shelf Life

Year

20

       MECHANICAL DATA OF VACUUM SWITCH EQUIPPED WITH THE INTERRUPTERS 

Data

Unit     

Value

Average Opening Speed

m/s                   

0.5±0.15            

Average Closing Speed

m/s

0.25±0.1

Contact Bounce Duration at Closing Operation

ms

≤3

Out of Simultaneity of Contact Closing and Opening

ms

≤1

Rated Contact Pressure

N

 

Max.rebound of contact at opening Operation

mm

2

Overtravel during opening

mm

≤2

Note: Meets or exceeds the electrical endurance requirements for IEC60470 and GB/T14808-2001.

vacuum interrupter